Product Name | SG65 Miniature Circuit Breaker |
Poles | 1p/2p/3p/4p |
Breaking Capacity | 6KA |
Rated Current | 6,10,16,20,25,32,40,50,63A |
Certificates | CE/ISO1009-1/CCC |
Rated Voltage | 230/400V |
Frequency | 50/60Hz |
Mechniacal Life | 10,000 times |
Flame-redardant | PA66 nylon material |
Standard | IEC1009-1 |
Application
SG65-63 high breaking miniature circuit breaker has the features of structure advanced, performance reliable, breaking capacity high, appearance elegant and its shell and parts are made of material with impact resistance, strong flame-retardant feature.
Technical Parameters
Rated voltage(V) | Poles | Rated current (A) | Rated short circuit breaking capacity | |
Test breaking capacity(KA) | Power factor | |||
230 | 1,2 | 6,10,16,20, | 6 | 0.65~0.70 |
230/400 | 1,2 | 25,32, | 6 | |
400 | 2,3,4 | 40 | 6 | |
230 | 1,2 | 50,63 | 6 | 0.75~0.80 |
230/400 | 1,2 | 6 | ||
400 | 2,3,4 | 6 |
Remark:
1.mechanical life:10,000 times(off-on)
2.heat resistance: category 2 (temperature 55°C,relative humidity 95%).
3.wiring is terminal with clamp, cable dia.:25mm²
Current Release Character Diagram
Test current(A) | Rated current(A) | Requested time | Result | Start station | Remark |
1.13In | all | t>=1h | Don't trip | Cool | |
1.45In | All | T<1h | trip | heat | Current ascends the requested value stably in 5s |
2.55In | In<=32A | 1s<t<60s | trip | Cool | Auxiliary switch closed, power is on |
2.55In | In>32A | 1s<t<120s | trip | Cool | Auxiliary switch closed, power is on |
5In(Cmode) | All | t>=0.1s | Don't trip | Cool | Auxiliary switch closed, power is on |
10In(Cmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |
10(Dmode) | All | t>=0.1s | Don't trip | Cool | Auxiliary switch closed, power is on |
14In(Dmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |